Gravel Expanse of Substation Switchyard Area on the Coast of South Bali
Keywords:
Gravel Stone Overlay, Regosol Soil, Step Tension, Touch TensionAbstract
As a security for equipment and people around the substation, a gravel bed is needed. The results of this study are to determine the thickness of the gravel overlay in the switchyard area of the substation with the texture of the regosol soil so that the equipment and people around it are avoided from the current of disturbance that flows when a disturbance occurs, and the results of this study can be useful as a reference for the installation of gravel in the construction of the substation in the location of the regosol soil texture. The method used in this study is to use descriptive quantitative analysis. The results of the study were obtained that the thickness of gravel stones of 0.15 meters to 0.17 meters has the best value in wet and dry conditions in the texture of the regosol soil on the coast of Kuta, the coast of Gianyar and the coast of Klungkung.
References
[1]. Agus Pranoto, Hans Tumaliang, Glanny M.Ch. Mangindaan. Analisa Sistem Pentanahan Gardu Induk Teling Dengan Konstruksi Grid (Kisi-kisi) Jurnal Teknik Elektro dan Komputer Vol. 7, No.3, Juli-Oktober 2018, ISSN : 2301 – 8402.
[2] Hardi, S., Harahap, IS., Rangkuti, HH., Wirasari, RR. Tegangan Potensial Tanah Pada Sistem Pentanahan Gardu Induk Dua Lapisan. SEMNASTEK UISU 2023. ISBN : 2987-6818.
[3] Setiono, DA. 2016. Studi Pengaruh Kandungan Air Tanah Terhadap Tahanan Jenis Tanah Lempung (Clay). Jurnal Ilmiah Teknik Elektro Universitas Tanjungpura. Hal. 1-8.
[4] Rauf, R. 2014. Studi Pemanfaatan Listrik Untuk Menaiikkan Tahanan Pentanahan Kaki Manusia Pada Area Gardu Induk PT Semen Padang. Jurnal Teknik Elektro ITP Volume 3 No. 2; Juli 2014.
[5] Quentin MP, P., Partha, CGI., Janardana, IGN. 2020. Optimasi Perencanaan Sistem Pembumian Pada Rencana Pembangunan Gas Insulated Substation 150 kV Pecatu. Jur Jurnal SPEKTRUM Vol. 7, No. 1 Maret 2020.
[6] Latiefa,RF., Zakir,I., Subekti, M. 2018. Pengaruh Kelembaban Tanah Terhadap Tahanan Pentanahan Studi Kasus Pada Gardu Induk Kemayoran 150 kV. | Jurnal ofElectricalandVocationalEducationand Technology, Vol.3, No.1, Juni 2018, 18-23.
[7] Andira, R. 2018. Analisis Sistem Pertanahan Grid pada Gardu Induk 2 x 500 MVA Galang. Medan: Universitas Sumatra Utara.
[8] Mahadewi, KM., Janardana, IGN., Wijaya, IWA,. 2019. Analisis Tegangan Langkah dan tegangan Sentuh Serta erencanaan Sistem Pembumian Pada Pembangunan Substation VVIP. Di Bandara Internasional I Gusti Ngurah Rai Bali. Journal SPEKTRUM Volume 6, No. 1 Maret 2019. Jimbaran : Program Studi Teknik Elektro Universitas Udayana.
[9] Suartika, IM. 2017. Sistem Pembumian (Grounding) Dua Batang Sistem Pengaman Tenaga Listrik. Bali: Universitas Udayana Bali.
Downloads
Published
Issue
Section
License
Copyright (c) 2025 International Journal of Sciences: Basic and Applied Research (IJSBAR)

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Authors who submit papers with this journal agree to the following terms.